11kV Metal-Enclosed Ring Main Unit HXGN15

The HXGN15-11 is a fixed, indoor, medium-voltage ring main unit (RMU) designed for 11kV, 50Hz AC power distribution systems. It utilizes SF6 load-break switches, FKRN12 load-break switches, or VS1 vacuum circuit breakers as the primary switching components. Suitable for ring main or radial terminal power supply configurations, it facilitates the distribution, control, and protection of electrical energy and can be integrated into prefabricated substations or switching stations.

The enclosure is constructed from galvanized steel, featuring a compact design with a small footprint. It comes equipped with a comprehensive mechanical "five-prevention" interlocking system, which reliably prevents operational errors—such as unauthorized switching, closing the switch while the grounding connection is engaged, or opening the cabinet door while the equipment is energized—thereby ensuring the safety of operations and maintenance personnel. The unit supports both manual and electric operation, offers flexible configuration options, and can be equipped with fuses to provide transformer protection.

Product Details

Feature

  • High Current and High Breaking Capacity: With a rated current of up to 2500A and a short-circuit breaking capacity of up to 40kA, it is well-suited for industrial power distribution applications characterized by high loads and high fault-level potential.
  • Versatile Functional Units: The HXGN15 can be configured with load-break switch units and fixed-type vacuum circuit breaker units, addressing diverse power distribution requirements such as ring-main feeders, outgoing circuits, and transformer protection.
  • Cost-Effective Project Solutions: For projects where installation space is not strictly constrained, an air-insulated (AIS) design offers a more cost-competitive alternative to fully gas-insulated ring main units (RMU).
  • Flexible Component Configuration: Depending on project budgets and brand preferences, users can select either standard components provided by Aikai or products from specified brands—such as ABB or Schneider—allowing for a flexible balance between performance and cost.
  • Reliable interlocking: Robust mechanical interlocks are provided between the circuit breaker, disconnector, earthing switch, and cabinet door, fully implementing the "five-prevention" safety functions.

Usage conditions

  • Ambient temperature: -15°C to +40°C
  • Altitude: ≤1000m (special customization required for higher altitudes)
  • Relative humidity: Daily average ≤95%, monthly average ≤90%
  • Seismic intensity: Not exceeding 8 degrees; free from severe vibration or impact
  • Installation environment: Indoor; free from explosive or corrosive gases, and without significant conductive dust pollution

Technical Data

NO
Name
Unit
Data
1 Rated Voltage
kV
7.2/10/11/12
2 Rated frequency
Hz
50/60
3 Rated current
A
630/1250/1600/2000/2500
4 Rated short-circuit breaking current
kA
20/25/31.5
5 Size
mm
Fixed-type 500 × 900 × 1850/Push-type700×700×700
6 Weight
KG
220-750

For customizing any other special sizes, please contact our salesman for more information.